Standards & Regulations / British Standard BS 5839-6:2019

Building Regs.jpg

British Standards BS 5839-6:2019 – What’s changed?
 

The BSI’s recent update of the domestic fire detection and alarm system standard, specifically Part 6 of BS 5839, outlines the code of practice for the design, installation, commissioning and maintenance of fire detection and fire alarm systems in domestic properties. Here Ian Ballinger, Certification Manager for FireAngel, outlines the key updates professionals should be aware of in order to ensure constant compliance when specifying, installing and maintaining fire detection systems in domestic properties.

 

First launched in 1995, British Standard BS 5839-6 has long established itself as a key reference standard for specifiers, architects and fire safety personnel, outlining the specific systems that should be installed for the purpose of life safety and property protection. Covering the implementation of fire precautions in domestic premises, including HMOs and sheltered housing, throughout both the dwelling units and common areas, the Standard is applicable to both new build and materially altered dwellings (in conjunction with regional building regulations) as well as existing properties. The recommendations can be applied to the fire detection components of combined domestic fire and intruder alarm systems, or fire and social alarm systems.

 

New recommendations have been added for fire detection in supported housing in particular, whilst revised guidance on the installation of communal fire alarm systems in purpose-built blocks of flats has also been introduced. The Standard has also been updated to reflect the updates made to Part 1 in 2017, which addresses non-domestic premises, combined with any other updates made to other Standards since the last full revision.

 

Below we outline the key changes to the BS 5839-6 Standard and the areas professionals should be aware of to ensure they’re offering individuals the highest standard of fire protection throughout all types of domestic properties. This applies to architects, building professionals, installers and enforcing authorities.

 

Revised system grading for fire detection and fire alarm systems:

Whilst BS 5839-6 has previously been split into six varying Grades, each outlining the level of protection appropriate for certain properties and their corresponding levels of risk, the new update has altered the six sections, removing Grade B and Grade E, whilst Grade D and Grade F have been split into Grade D1 / Grade D2 and Grade F1 / Grade F2 respectively. Grade C has been revised and its recommendations expanded.

The new grading system is as follows:

Grade A

Separate detectors, sounders and central control and indicating equipment with back-up power supply that conforms to British Standards BS EN 54.

Grade C

Separate detectors and sounders that are mains powered with back-up power supply and central control equipment.

Grade D1

A system of one or more mains powered detectors, each with a tamper‑proof standby supply consisting of a battery or batteries (such as FireAngel’s SM-SN-1 alarm).

Grade D2

A system of one or more mains-powered detectors, each with an integral standby supply consisting of a user‑replaceable battery or batteries. (such as FireAngel’s SW1-PF-T alarm). 

Grade F1

A system of one or more battery-powered detectors powered by a tamper‑proof primary battery or batteries (such as FireAngel’s ST-622, ST-750 alarm). 

Grade F2

A system of one or more battery-powered detectors powered by a user‑replaceable primary battery or batteries. (such as FireAngel’s SB1-T alarm).

Grades B and E have become obsolete in the latest version.

 

Professionals should adhere to the above grades when designing, constructing and managing fire detection and fire alarm systems in domestic properties. They should also be aware of the revisions made to Table 1 of The Standard, which outlines the minimum grade and category of system that should be installed to provide protection of life in typical premises. The updates have been made to reflect current living conditions.

 

In conjunction with Table 1, a new table has also been created, which outlines the recommended testing and servicing by grade to prevent the blocking or delaying of fire alarm signals transmitted via social alarm systems in sheltered housing to an alarm receiving centre.

 

3 categories for fire detection and fire alarm systems :

With regard to categories, the standard of protection in sheltered housing flats has been increased from Category LD2 to Category LD1, positioning it as a higher potential risk. To meet LD1 requirements, the installation of a fire detection system is required throughout the premises - this includes all rooms (and circulation areas that form part of the escape routes) except toilets, bathrooms and shower rooms.

The three categories for fire detection and fire alarm systems are listed below and outline where fire detection systems should be installed:

LD1 Maximum Protection

LD Grades

all areas where a fire could start

Alarms in all circulation spaces that form part of escape routes and all areas where a fire might start, but not bathrooms, shower rooms or toilets, such as:

  • Hallway
  • Landing
  • Living Room
  • Kitchen 
  • Bedroom
  • Airing / Meter Cupboards
  • Loft
  • Garage

LD1-High Protection for homes

LD2 Additional Protection

LD Grades-1circulation spaces and high-risk rooms

Alarms in all circulation spaces that form part of escape routes and rooms or areas that present a high fire risk such as:

  • Hallway

  • Landing

  • Living Room

  • Kitchen 

LD2 Protection

LD3 Minimum Protection

LD Grades-2

escape routes only

Alarms in all circulation spaces that form part of escape routes such as:

  • Hallway

  • Landing

LD3 - Minimum Protection diagram in house

 

Additional Guidance 

  • The latest updates also outline the recommendation of optical smoke alarms or Multi-Sensor fire alarms featuring an optical sensor, such as FireAngel’s SM-SN-1 (Grade D1), ST-622 (Grade F1), to be installed in circulation areas such as hallways and landings.
  • Heat alarms should also be installed in kitchens to provide appropriate protection.
  • Interconnected alarms should also be installed throughout a property, dependent on the specific grade, through hard-wiring or wireless connections.

 

By following the latest changes to BS 5839-6, professionals can ensure the systems they install are not only fit for purpose for current living environments within domestic premises, but also ensure individuals are provided with the highest forms of protection available, contributing to the reduction in the number of fire deaths and injuries that occur each year.

 


 Further Reading:

  • BSI 'Why we’ve updated the domestic fire detection and alarm systems standard' - Click here

Our Latest Posts

FireAngel Predict: The Future of Fire Safety

As our flagship product FireAngel Predict launches later this year we sat down with Chief Product Officer, Nick Rutter, to give you an insight into

Fire Safety Requirements for New Build Properties

Fire safety is one of the key sections within the Building Regulations, which outline the requirements needed to provide an early warning of fire,

How To Install Hardwire and Wireless Smoke Alarms in a Mixed System

Ways to interlink alarms FireAngel Wi-Safe 2 provides flexible wireless solutions for both hard-wired and battery systems. Up to 50 smoke, heat or

Your Guide To Fire Safety In Student Accommodation

For students going to university for the first time, often the last thing they will think about is fire safety. However, student accommodation can be

Scotland Updating Fire Safety Legislation following Grenfell Tragedy

Scotland has long since led the way with carbon monoxide and fire safety legislation in the UK. For example, Building Regulations in England and

Alarm Control Unit - An Ideal Solution To Remotely Testing Smoke Alarms

What are the benefits of an alarm control unit?  The FireAngel Alarm Control Unit (WTSL-SN-1) allows you to remotely test a variety of smoke, carbon

Contact Us.jpg

We're Always Ready to Help!

Get Support